{"id":8780,"date":"2018-04-09T08:02:22","date_gmt":"2018-04-09T08:02:22","guid":{"rendered":"https:\/\/www.tarluz.com\/?p=8780"},"modified":"2018-04-09T08:12:03","modified_gmt":"2018-04-09T08:12:03","slug":"inspect-and-clean-high-density-mpo-mtp-connector","status":"publish","type":"post","link":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/","title":{"rendered":"Inspect and Clean High Density MPO\/MTP Connector"},"content":{"rendered":"<p>Before you install the MPO connectors in the data cnter, it is essential that all the fiber end-faces and the ferrule are really clean. especially when you thinking about lining up 12, 16, 24 or 32 pieces of 9um fibers in one or two rows, it requires tremendous precision. Any dirts in the mix on one of your fiber end-faces or on the ferrule might affect the performance of the optical link, cause system failurs.<\/p>\n<p>Picture a scenario in which the above-referenced scenario takes place. Dirt and air gaps have compromised the first 7 of the 12 fibers in an MPO connector. In such a scenario, testing fibers 8 through 12 would show no problems; those fibers could be put into service. However, if you wanted to add traffic later to fibers 1, 2, 3, and 4, the tests would show too much loss or too much reflection, which would require taking apart the connector to clean it and dropping any traffic on the lower fibers.<img loading=\"lazy\" decoding=\"async\" class=\"wp-image-2265 alignright\" src=\"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg\" alt=\"\" width=\"300\" height=\"300\" \/><\/p>\n<p>To avoid this kind of problem, Viavi recommends the \u201cInspect Before You Connect\u201d approach, a practice that is consistent with IEC standards.<\/p>\n<p>The concept is simple: First inspect all the fiber endfaces. If the endface is not dirty, you\u2019re good to go. If there\u2019s any contamination, you clean it. Then you inspect it again. Always re-inspect because it\u2019s the only way to know if your cleaning process was effective. Never connect until the fiber endface is clean. Never clean first; there\u2019s no point in cleaning something that is already clean because you don\u2019t want to touch that fiber endface more than necessary.<\/p>\n<p>To ensure that the system is free of contamination, both sides of every connection must be clean. Patch cords are easy to access and view compared to the fiber inside the bulkhead, which is frequently overlooked. That\u2019s typically because the installer doesn\u2019t have the right tool, but it\u2019s a mistake to skip it. The bulkhead side may only be half of the connection, but it is far more likely to be dirty and problematic.<\/p>\n<p>The IEC 61300-3-35 standard sets the inspection requirements for connector quality. It applies to both simplex and MPO connectors, but with MPO connectors, only two zones matter: the core and the cladding.<\/p>\n<p>Clickers are good for cleaning endfaces during network installations as they are effective for both cassettes and patch cords.<\/p>\n<p>MPO connectors tend to be more prone to static buildup than simplex connectors. For this reason, using a wet-to-dry cleaning method is preferred.<\/p>\n<p>Viavi recommends applying a small amount of cleaning fluid to an optical-grade wipe, then touching the cleaning tip of the clicker to the wet spot on the wipe. Never apply the cleaning fluid directly to the cleaning ribbon.<\/p>\n<p>An adapter is used to connect an unpinned\/female adapter (key up) with a pinned\/male adapter (key down), ensuring the pins line up to create a physical connection.<\/p>\n<p>&nbsp;<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Before you install the MPO connectors in the data cnter, it is essential that all the fiber end-faces and the ferrule are really clean. especially when you thinking about lining up 12, 16, 24 or 32 pieces of 9um fibers in one or two rows, it requires tremendous precision. Any dirts in the mix on [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[399],"tags":[],"class_list":["post-8780","post","type-post","status-publish","format-standard","hentry","category-data-center"],"yoast_head":"<!-- This site is optimized with the Yoast SEO Premium plugin v23.3 (Yoast SEO v27.4) - https:\/\/yoast.com\/product\/yoast-seo-premium-wordpress\/ -->\n<title>Inspect and Clean High Density MPO\/MTP Connector - TARLUZ - FIBER OPTIC SUPPLIERS<\/title>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/\" \/>\n<meta property=\"og:locale\" content=\"fr_FR\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"Inspect and Clean High Density MPO\/MTP Connector\" \/>\n<meta property=\"og:description\" content=\"Before you install the MPO connectors in the data cnter, it is essential that all the fiber end-faces and the ferrule are really clean. especially when you thinking about lining up 12, 16, 24 or 32 pieces of 9um fibers in one or two rows, it requires tremendous precision. Any dirts in the mix on [&hellip;]\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/\" \/>\n<meta property=\"og:site_name\" content=\"TARLUZ - FIBER OPTIC SUPPLIERS\" \/>\n<meta property=\"article:published_time\" content=\"2018-04-09T08:02:22+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2018-04-09T08:12:03+00:00\" \/>\n<meta property=\"og:image\" content=\"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg\" \/>\n<meta name=\"author\" content=\"TARLUZ.COM\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"\u00c9crit par\" \/>\n\t<meta name=\"twitter:data1\" content=\"TARLUZ.COM\" \/>\n\t<meta name=\"twitter:label2\" content=\"Dur\u00e9e de lecture estim\u00e9e\" \/>\n\t<meta name=\"twitter:data2\" content=\"2 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/\"},\"author\":{\"name\":\"TARLUZ.COM\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/#\\\/schema\\\/person\\\/5740f1b7210de5d651317604459f2fb1\"},\"headline\":\"Inspect and Clean High Density MPO\\\/MTP Connector\",\"datePublished\":\"2018-04-09T08:02:22+00:00\",\"dateModified\":\"2018-04-09T08:12:03+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/\"},\"wordCount\":489,\"commentCount\":0,\"image\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.tarluz.com\\\/wp-content\\\/uploads\\\/2016\\\/09\\\/MPO-MTP-Cleaner-1.jpg\",\"articleSection\":[\"Data Center\"],\"inLanguage\":\"fr-FR\"},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/\",\"url\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/\",\"name\":\"Inspect and Clean High Density MPO\\\/MTP Connector - TARLUZ - FIBER OPTIC SUPPLIERS\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/#website\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#primaryimage\"},\"image\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#primaryimage\"},\"thumbnailUrl\":\"https:\\\/\\\/www.tarluz.com\\\/wp-content\\\/uploads\\\/2016\\\/09\\\/MPO-MTP-Cleaner-1.jpg\",\"datePublished\":\"2018-04-09T08:02:22+00:00\",\"dateModified\":\"2018-04-09T08:12:03+00:00\",\"author\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/#\\\/schema\\\/person\\\/5740f1b7210de5d651317604459f2fb1\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#breadcrumb\"},\"inLanguage\":\"fr-FR\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/\"]}]},{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#primaryimage\",\"url\":\"https:\\\/\\\/www.tarluz.com\\\/wp-content\\\/uploads\\\/2016\\\/09\\\/MPO-MTP-Cleaner-1.jpg\",\"contentUrl\":\"https:\\\/\\\/www.tarluz.com\\\/wp-content\\\/uploads\\\/2016\\\/09\\\/MPO-MTP-Cleaner-1.jpg\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/data-center\\\/inspect-and-clean-high-density-mpo-mtp-connector\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"Inspect and Clean High Density MPO\\\/MTP Connector\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/#website\",\"url\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/\",\"name\":\"TARLUZ - FIBER OPTIC SUPPLIERS\",\"description\":\"DEDICATED IN FIBER OPTIC INDUSTRY\",\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"fr-FR\"},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/#\\\/schema\\\/person\\\/5740f1b7210de5d651317604459f2fb1\",\"name\":\"TARLUZ.COM\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"fr-FR\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g\",\"caption\":\"TARLUZ.COM\"},\"url\":\"https:\\\/\\\/www.tarluz.com\\\/fr\\\/author\\\/admin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO Premium plugin. -->","yoast_head_json":{"title":"Inspect and Clean High Density MPO\/MTP Connector - TARLUZ - FIBER OPTIC SUPPLIERS","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/","og_locale":"fr_FR","og_type":"article","og_title":"Inspect and Clean High Density MPO\/MTP Connector","og_description":"Before you install the MPO connectors in the data cnter, it is essential that all the fiber end-faces and the ferrule are really clean. especially when you thinking about lining up 12, 16, 24 or 32 pieces of 9um fibers in one or two rows, it requires tremendous precision. Any dirts in the mix on [&hellip;]","og_url":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/","og_site_name":"TARLUZ - FIBER OPTIC SUPPLIERS","article_published_time":"2018-04-09T08:02:22+00:00","article_modified_time":"2018-04-09T08:12:03+00:00","og_image":[{"url":"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg","type":"","width":"","height":""}],"author":"TARLUZ.COM","twitter_card":"summary_large_image","twitter_misc":{"\u00c9crit par":"TARLUZ.COM","Dur\u00e9e de lecture estim\u00e9e":"2 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#article","isPartOf":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/"},"author":{"name":"TARLUZ.COM","@id":"https:\/\/www.tarluz.com\/fr\/#\/schema\/person\/5740f1b7210de5d651317604459f2fb1"},"headline":"Inspect and Clean High Density MPO\/MTP Connector","datePublished":"2018-04-09T08:02:22+00:00","dateModified":"2018-04-09T08:12:03+00:00","mainEntityOfPage":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/"},"wordCount":489,"commentCount":0,"image":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#primaryimage"},"thumbnailUrl":"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg","articleSection":["Data Center"],"inLanguage":"fr-FR"},{"@type":"WebPage","@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/","url":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/","name":"Inspect and Clean High Density MPO\/MTP Connector - TARLUZ - FIBER OPTIC SUPPLIERS","isPartOf":{"@id":"https:\/\/www.tarluz.com\/fr\/#website"},"primaryImageOfPage":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#primaryimage"},"image":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#primaryimage"},"thumbnailUrl":"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg","datePublished":"2018-04-09T08:02:22+00:00","dateModified":"2018-04-09T08:12:03+00:00","author":{"@id":"https:\/\/www.tarluz.com\/fr\/#\/schema\/person\/5740f1b7210de5d651317604459f2fb1"},"breadcrumb":{"@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#breadcrumb"},"inLanguage":"fr-FR","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/"]}]},{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#primaryimage","url":"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg","contentUrl":"https:\/\/www.tarluz.com\/wp-content\/uploads\/2016\/09\/MPO-MTP-Cleaner-1.jpg"},{"@type":"BreadcrumbList","@id":"https:\/\/www.tarluz.com\/fr\/data-center\/inspect-and-clean-high-density-mpo-mtp-connector\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.tarluz.com\/fr\/"},{"@type":"ListItem","position":2,"name":"Inspect and Clean High Density MPO\/MTP Connector"}]},{"@type":"WebSite","@id":"https:\/\/www.tarluz.com\/fr\/#website","url":"https:\/\/www.tarluz.com\/fr\/","name":"TARLUZ - FIBER OPTIC SUPPLIERS","description":"DEDICATED IN FIBER OPTIC INDUSTRY","potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.tarluz.com\/fr\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"fr-FR"},{"@type":"Person","@id":"https:\/\/www.tarluz.com\/fr\/#\/schema\/person\/5740f1b7210de5d651317604459f2fb1","name":"TARLUZ.COM","image":{"@type":"ImageObject","inLanguage":"fr-FR","@id":"https:\/\/secure.gravatar.com\/avatar\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/6e1d411095ca6ac0a50a32b0e09d4e99f1d22d747cb3e84f95fe301bdc28d113?s=96&d=blank&r=g","caption":"TARLUZ.COM"},"url":"https:\/\/www.tarluz.com\/fr\/author\/admin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/posts\/8780","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/comments?post=8780"}],"version-history":[{"count":5,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/posts\/8780\/revisions"}],"predecessor-version":[{"id":8791,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/posts\/8780\/revisions\/8791"}],"wp:attachment":[{"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/media?parent=8780"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/categories?post=8780"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.tarluz.com\/fr\/wp-json\/wp\/v2\/tags?post=8780"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}